Technical Data SheetÂ
Range of product | Harmony Electromechanical Relays |
---|---|
Series name | Miniature |
Product or component type | Plug-in relay |
device short name | RXM |
Contacts type and composition | 4 C/O |
[Uc] control circuit voltage | 110 V DC |
Status LED | With |
Control type | Lockable test button |
Utilisation coefficient | 20 % |
Shape of pin | Flat |
---|---|
[Ui] rated insulation voltage | 250 V conforming to IEC 300 V conforming to CSA 300 V conforming to UL |
Contacts material | AgNi |
[Ie] rated operational current | 3 A at 28 V (DC) NC conforming to IEC 3 A at 250 V (AC) NC conforming to IEC |
Continuous output current | 5 A |
maximum switching voltage | 250 V conforming to IEC |
resistive rated load | 6 A at 250 V AC 6 A at 28 V DC |
maximum switching capacity | 1500 VA/168 W |
minimum switching capacity | 170 mW at 10 mA, 17 V |
operating rate | <= 1200 cycles/hour under load <= 18000 cycles/hour no-load |
Mechanical durability | 10000000 cycles |
electrical durability | 100000 cycles for resistive load |
average coil consumption | 0.9 W |
drop-out voltage threshold | >= 0.1 Uc |
operate time | 20 ms |
release time | 20 ms |
average coil resistance | 13440 Ohm at 20 °C +/- 10 % |
rated operational voltage limits | 88…121 V DC |
Safety reliability data | B10d = 100000 |
Protection category | RT I |
test levels | Level A group mounting |
Operating position | Any position |
Net weight | 0.037 kg |
Device presentation | Complete product |
Dielectric strength | 1300 V AC between contacts with micro disconnection 2000 V AC between coil and contact with basic insulation 2000 V AC between poles with basic insulation |
---|---|
product certifications | GOST CE UL Lloyd’s CSA |
Standards | CSA C22.2 No 14 UL 508 EN/IEC 61810-1 |
Ambient air temperature for storage | -40…85 °C |
ambient air temperature for operation | -40…55 °C |
vibration resistance | 3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation 5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating |
IP degree of protection | IP40 conforming to EN/IEC 60529 |
shock resistance | 10 gn for in operation 30 gn for not operating |
Pollution degree | 2 |