250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
Contacts material
AgNi
[Ie] rated operational current
3 A at 28 V (DC) NC conforming to IEC
3 A at 250 V (AC) NC conforming to IEC
Continuous output current
5 A
maximum switching voltage
250 V conforming to IEC
resistive rated load
6 A at 250 V AC
6 A at 28 V DC
maximum switching capacity
1500 VA/168 W
minimum switching capacity
170 mW at 10 mA, 17 V
operating rate
<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Mechanical durability
10000000 cycles
electrical durability
100000 cycles for resistive load
average coil consumption
0.9 W
drop-out voltage threshold
>= 0.1 Uc
operate time
20 ms
release time
20 ms
average coil resistance
13440 Ohm at 20 °C +/- 10 %
rated operational voltage limits
88…121 V DC
Safety reliability data
B10d = 100000
Protection category
RT I
test levels
Level A group mounting
Operating position
Any position
Net weight
0.037 kg
Device presentation
Complete product
Environment
Dielectric strength
1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
product certifications
GOST
CE
UL
Lloyd’s
CSA
Standards
CSA C22.2 No 14
UL 508
EN/IEC 61810-1
Ambient air temperature for storage
-40…85 °C
ambient air temperature for operation
-40…55 °C
vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
Be the first to review “Miniature plug in relay Harmony, 6A, 4CO” Cancel reply
Documentation & RFQ readiness
BOLTON sources and supplies to specification. Documentation availability depends on the product, its manufacturer/supplier source and your stated requirement, and can be confirmed during quotation. To get an accurate quote quickly, include:
The exact manufacturer part number (MPN) and quantity required
Any drawing, specification or standard that applies, where relevant
Required documentation — e.g. certificate of conformity, datasheet, test report, SDS/TDS, calibration certificate or traceability, where applicable
Reviews
There are no reviews yet.